Industrial protocols and technologies
PROFINET, PROFIBUS, Siemens S7, OPC UA, MQTT, Modbus, Node-RED, Grafana, historians, OT DMZ and IEC 62443. What each one does, when it is chosen and where it most often gets stuck in the field.
Vendor-independentNo reseller claims
The right protocol and architecture for the right need
Whether a technology can be used in a project is decided by looking at the device model, firmware, licence and the configuration on site. A brochure is not enough.
PROFINET
Cyclic and event-based communication between the controller and remote I/O, drives and HMIs. It uses standard Ethernet infrastructure; in most applications the RT channel is sufficient.
What to watch out for
IRT and TSN-based communication requires hardware and configuration support; it should not be assumed in every installation. If the device name/IP plan and GSDML management are not kept in order from the start, troubleshooting takes hours.
PROFIBUS DP / PA
Remote I/O and drive communication (DP, RS-485) and process instrumentation (PA) in existing plants.
What to watch out for
Segment length, baud rate, termination and shielding rules must be followed; termination is the most common fault in the field. DP/PN couplers can be used for a gradual migration to PROFINET.
Siemens S7 (S7-1200 / S7-1500)
Access to PLC data via OPC UA (depending on model, firmware and licence), S7 communication or a gateway.
What to watch out for
Project settings such as PUT/GET access and optimised block access directly determine the access method; these settings are not changed without the project owner’s approval.
ET200SP and SINAMICS
Typical IO devices on a PROFINET network; their diagnostic information is the first place to look in the console when communication fails.
What to watch out for
When replacing a device, name assignment, firmware and GSDML consistency should follow a written procedure.
SCALANCE and industrial switches
DIN-rail mounted switches for the field and cell level with a wide temperature range and redundant power; redundancy features such as MRP and PROFINET diagnostics.
What to watch out for
We choose the model according to technical criteria; we make no claim of being a manufacturer’s reseller or partner.
Modbus RTU / TCP
Register-based communication found in energy analysers, drives, compressors and many auxiliary devices.
What to watch out for
No authentication or encryption. The address map, data types and byte order must be documented and network access restricted.
SECURE INTEROPERABILITY STANDARD
OPC UA
Typed data model, certificate-based identity, signing and encryption; client/server and PubSub communication (IEC 62541).
What to watch out for
If the security mode, certificate management and user permissions are not configured, these features remain on paper only.
MQTT
Lightweight telemetry distribution via a broker; edge-to-platform integration with QoS, retain and Last Will.
What to watch out for
The topic hierarchy, TLS and per-user/per-topic access rules should be designed from the start. Fixing them later is difficult.
Node-RED
Data transformation, protocol conversion and rapid prototyping at the edge.
What to watch out for
If it is to be used in production, responsibility for versions, backups, access and maintenance must be defined in writing.
Grafana
Displaying production, energy and network monitoring data on role-based dashboards and generating alerts.
What to watch out for
Indicator definitions and data accuracy must be clear before the dashboard. Wrong data is still wrong in a beautiful chart.
Historians and edge buffering
Storing time-stamped production data; keeping data at the edge when the connection drops and forwarding it later (store-and-forward).
What to watch out for
Buffering is not built into every device; capacity and resend behaviour should be tested by pulling the cable.
OEE, MES and SAP / ERP
The flow of work orders, production confirmations, downtime and scrap data between layers following the ISA-95 model; OEE calculation.
What to watch out for
Development inside the ERP/MES is the job of the relevant product consultant; we handle the field, middleware and security side.
OT DMZ and VLANs
Logical separation with VLANs, access control between zones with firewalls, and a controlled transition zone between IT and OT with an OT DMZ.
What to watch out for
A VLAN on its own is not access control. Rules should be documented with their justification and reviewed at regular intervals.
INTERNATIONAL STANDARD SERIES FOR OT SECURITY
ISA/IEC 62443
A reference for OT security architecture with the zone and conduit approach, risk assessment and target security levels.
What to watch out for
Our services are architecture and implementation based on these principles; they are not certification or an independent conformity assessment.
Technology and product names are used to explain solution areas; they do not claim guaranteed integration or authorised representation for all brands and products. Sources: PI – PROFINET Technology Description, OPC Foundation – What is OPC?, ISA – ISA/IEC 62443 Series.
Industrial Ethernet, PROFINET and data protocols are not the same thing
| Concept | What it is | What it is not |
|---|---|---|
| Industrial Ethernet | Ethernet infrastructure used in the field and suited to environmental conditions | An automation protocol in its own right |
| PROFINET | A real-time automation protocol running over Ethernet | “Normal Ethernet” that works flawlessly on any switch and topology |
| OPC UA | An interoperability standard with a typed data model and security | A fast I/O protocol that replaces the control loop |
| MQTT | Publish/subscribe messaging via a broker | A system that defines a data model or security by itself |
| VLAN | A method of logically separating a network | A security control that governs access between zones |
Let's map the technologies on your site together
Tell us about your installed equipment and your goal; we will propose suitable protocol and architecture options with our reasoning.