Online PLC Data Buffer Sizing

Calculates how large the on-site buffer must be so data is not lost when the central link drops.

  • Data is processed in your browser and not sent to a server

Tool

1 = every second; 0.1 = every 10 seconds.

REAL/DINT 4, LREAL 8, BOOL 1.

Below 100 % with report-by-exception (deadband).

File/database format headroom.

Optional.

What does this tool do?

An edge gateway or PLC buffers measurements locally when the historian/cloud link drops (store and forward). When the buffer is full the oldest data is deleted and production records get gaps. The tool gives hourly data volume from tag count and sample rate, the memory needed for a target outage and how long existing memory lasts.

How to use it

  1. Enter tag count and samples per second per tag (1 = every second, 0.1 = every 10 seconds).
  2. Enter record size (value, timestamp, id/quality bytes) and the share of samples stored.
  3. Enter the outage duration to cover and, if known, available memory; press Run.

Fields

Tags
Samples/s (per tag)
1 = every second; 0.1 = every 10 seconds.
Value bytes
REAL/DINT 4, LREAL 8, BOOL 1.
Timestamp bytes
Id/quality bytes
Share of samples stored
Below 100 % with report-by-exception (deadband).
Outage to cover (hours)
Structure overhead
File/database format headroom.
Available memory
Optional.

Worked example

InputValue
Tags200
Samples/s (per tag)1
Value bytes4
Timestamp bytes8
Id/quality bytes2
Share of samples stored100
Outage to cover (hours)24
Structure overhead0
Available memory128

Expected result: 200 tags, 1 sample per second, 14-byte record: 2.8 kB/s, 241.92 MB for 24 hours; 128 MB lasts about 12.7 hours of outage.

An outage unnoticed over a weekend means data loss. Slowing sampling of low-priority tags to 10 seconds or storing only changes with a deadband extends the buffer several times.

Second scenario

InputValue
Tags1500
Samples/s (per tag)0.2
Value bytes4
Timestamp bytes8
Id/quality bytes2
Share of samples stored30
Outage to cover (hours)72
Structure overhead10
Available memory512

Expected result: 1,500 tags, every 5 seconds, 30 % changes, 72 hours: 359.25 MB; fits in 512 MB.

Method and assumptions

Record = value + timestamp + id/quality bytes. Bytes/s = tags × samples/s × stored share × record × (1 + overhead). Needed = bytes/s × hours × 3600. Duration with memory = memory / bytes/s / 3600.

Using the result and troubleshooting

Size the buffer for the longest expected outage (weekend, maintenance) and set a buffer fill alarm. Use the Historian Storage Calculator for the historian side.

Limits and common mistakes

  • Compression, batching and the gateway software's internal structures are not modelled; prefer vendor memory figures.

Frequently asked questions

What happens when the buffer is full?

Most gateways overwrite the oldest data (FIFO); some reject new data. Check which behaviour is configured.